Level 1 · Starter build

Budget AGM Starter wiring diagram

The lowest-cost way into van electrics: an AGM battery, a modest solar panel and alternator charging running a small fridge, lights and USB sockets. Everything is sized conservatively so the budget bank lasts.

Get access to your wiring diagram by email

Build your plan in the calculator, then open the link we email you to view diagrams and download a PDF.

Create my plan

Read and adapt this wiring plan

This example starts with 710 Wh of daily appliance demand. Trace each charging source to the battery, then follow each protected supply to its load and back through the return path. The table makes the drawing searchable and gives you a record to compare with your actual cable routes.

Cable sizes and protective devices below are calculated planning outputs for the stated assumptions. They need checking against equipment manuals, installation conditions, available fault current and the applicable standards. Changing route length, battery voltage or appliance demand can change the result. An AWG conversion alone is not an ampacity check.

  1. Replace example appliance hours with your measured or intended use. Check both daily energy and simultaneous power.
  2. Place equipment to preserve ventilation, access and manufacturer clearances. Measure each real cable route before ordering.
  3. Review the supply, protective device, cable and terminal ratings as one circuit. Check battery and charger limits together.
  4. Have mains switching, earthing and protective-device operation assessed for every supply mode before use.
  5. Keep the final drawing, settings, photographs and commissioning results with the van. Recheck them after an upgrade.
Download this diagram, cable schedule and parts PDF

Cable schedule and assumed routes

ConnectionCurrentOne-way lengthCableFuseVoltage drop
Leisure Battery Bank → Positive & Negative Busbars
positive
12.0 A0.5 m1 mm²15 A MEGA1.80%
Solar Array → MPPT Charge Controller
positive
17.0 A5 m4 mm²See protection schedule2.00%
MPPT Charge Controller → Positive & Negative Busbars
positive
45.0 A1.5 m10 mm²60 A MIDI / MEGA at busbar2.00%
Starter Battery / Alternator → DC-DC Charger
positive
48.0 A5 m25 mm²60 A MIDI at starter battery2.80%
DC-DC Charger → Positive & Negative Busbars
positive
40.0 A1.5 m10 mm²50 A MIDI at busbar1.80%
Positive & Negative Busbars → 12 V Fuse Box
positive
12.0 A2 m4 mm²15 A MIDI at busbar1.80%
12 V Fuse Box → Compressor Fridge (Small)
positive
3.8 A4 m1.5 mm²5 A Blade, way #13.00%
12 V Fuse Box → LED Spot Lights
positive
1.7 A6 m1 mm²3 A Blade, way #23.00%
12 V Fuse Box → Water Pump
positive
5.0 A5 m1.5 mm²7.5 A Blade, way #34.90%
12 V Fuse Box → USB Sockets
positive
0.8 A4 m1 mm²2 A Blade, way #40.90%
Leisure Battery Bank → Positive & Negative Busbars
negative
12.0 A0.5 m1 mm²See protection schedule1.80%
Solar Array → MPPT Charge Controller
negative
17.0 A5 m4 mm²See protection schedule2.00%
MPPT Charge Controller → Positive & Negative Busbars
negative
45.0 A1.5 m10 mm²See protection schedule2.00%
Starter Battery / Alternator → DC-DC Charger
negative
48.0 A5 m25 mm²See protection schedule2.80%
DC-DC Charger → Positive & Negative Busbars
negative
40.0 A1.5 m10 mm²See protection schedule1.80%
Positive & Negative Busbars → 12 V Fuse Box
negative
12.0 A2 m4 mm²See protection schedule1.80%
12 V Fuse Box → Compressor Fridge (Small)
negative
3.8 A4 m1.5 mm²See protection schedule3.00%
12 V Fuse Box → LED Spot Lights
negative
1.7 A6 m1 mm²See protection schedule3.00%
12 V Fuse Box → Water Pump
negative
5.0 A5 m1.5 mm²See protection schedule4.90%
12 V Fuse Box → USB Sockets
negative
0.8 A4 m1 mm²See protection schedule0.90%
Starter Battery / Alternator → DC-DC Charger
signal
0.5 A5 m0.75 mm²5 A Blade at ignition feed0.00%
MPPT Charge Controller → Leisure Battery Bank
signal
0.0 A1.5 m0.5 mm²See protection schedule0.00%
Positive & Negative Busbars → Chassis Bond
protective-earth
0.0 A1 m16 mm²See protection schedule0.00%

Appliance branch circuits

LoadCurrentRouteCableFuse
Compressor Fridge (Small)3.8 A4 m1.5 mm²5 A
LED Spot Lights1.7 A6 m1 mm²3 A
Water Pump5.0 A5 m1.5 mm²7.5 A
USB Sockets0.8 A4 m1 mm²2 A

Protection and installation parts

  • MEGA fuse 15 A + holder — 1; Main battery protection
  • Battery isolator switch — 1; 100 A+ continuous rating
  • Battery interconnect cables — 2; 1 mm² — identical length & cross-section per Victron guidance
  • Busbar pair (+/−) — 1 pair; ≥ 150 A, insulated covers
  • PV isolator switch — 1; DC-rated, ≥ 56 V
  • Solar roof gland + MC4 connectors — 1 set; Waterproof cable entry
  • MC4 extension cable pair — ≈ 2; Panel-to-panel and string-to-gland runs, UV-rated
  • MIDI fuse holders + fuses — 2; 60 A and 50 A for DC-DC run
  • 6-way 12 V blade fuse box — 1; With negative bus
  • 12 V blade fuse assortment — 1 set; 5 A, 3 A, 7.5 A, 2 A
  • D+ signal wire 0.75 mm² — ≈ 5 m; Ignition feed → DC-DC charger D+ terminal
  • 25 mm² cable — ≈ 11 m total; Red + black pair (lengths include 10 % spare)
  • 16 mm² cable — ≈ 3 m total; Red + black pair (lengths include 10 % spare)
  • 10 mm² cable — ≈ 7 m total; Red + black pair (lengths include 10 % spare)
  • 4 mm² cable — ≈ 16 m total; Red + black pair (lengths include 10 % spare)
  • 1.5 mm² cable — ≈ 40 m total; Red + black pair (lengths include 10 % spare)
  • 1 mm² cable — ≈ 46 m total; Red + black pair (lengths include 10 % spare)
  • Crimp lugs & ferrules — assorted; Sized to each cable; use a proper crimper
  • Heat shrink, grommets, cable clips — assorted; Abrasion protection everywhere a cable touches metal

Assumptions to review

  • System voltage 12 V (12 V nominal AGM). Voltage drop calculated round-trip (2 × run length) with copper resistivity 0.0175 Ω·mm²/m.
  • Voltage drop targets: ≤ 2.5 % main battery/charge runs (Victron), ≤ 3 % critical circuits (fridge, electronics), ≤ 5 % non-critical circuits (Blue Sea 3 %/10 % tiers, drawn conservatively).
  • Cable ampacities from UK thin-wall (≤ 6 mm²) and Hi-Flex battery cable (≥ 10 mm²) published ratings, free-air.
  • Fuses sized ≥ 1.25 × continuous load and ≤ cable ampacity, so the fuse always protects the cable.
  • Solar panel Voc ≈ 23 V and Isc ≈ W ÷ 19 estimated for typical "12 V" panels; cold-weather Voc factor 1.2. Check your actual panel datasheet.
  • Inverter DC current = W ÷ (11.5 V × 0.87 efficiency). Where a product manual states cable/fuse sizes, the manual takes precedence.
  • Circuit run lengths are typical-van defaults (fridge 4 m, lighting 6 m, etc.) — measure yours and resize if longer.
  • UK solar yield assumed 2.8 peak sun hours at 72 % system efficiency (annual average).